欢迎来到天天文库
浏览记录
ID:21483870
大小:24.50 KB
页数:3页
时间:2018-10-22
《出现i-o access error, writing,i-o access error, readingwhen writing 错误》由会员上传分享,免费在线阅读,更多相关内容在应用文档-天天文库。
1、出现I/Oaccesserror,writing,I/Oaccesserror,readingwhenwriting错误 Event66of500:EventID16#2943 I/Oaccesserror,writing Parea,double-wordaccess,Accessaddress:656 RequestedOB:I/OaccesserrorOB(OB122) Priorityclass:1 Externalerror,Incomingevent 02:09:25.096AM04/18/1994
2、 Event233of500:EventID16#2942 I/Oaccesserror,reading Parea,double-wordaccess,Accessaddress:166 RequestedOB:I/OaccesserrorOB(OB122) Priorityclass:1 Externalerror,Incomingevent 02:09:25.084AM04/18/1994 最佳答案 I/O访问错误组织块(OB122) 描述出现I/Oacc
3、esserror,writing,I/Oaccesserror,readingwhenwriting错误 Event66of500:EventID16#2943 I/Oaccesserror,writing Parea,double-wordaccess,Accessaddress:656 RequestedOB:I/OaccesserrorOB(OB122) Priorityclass:1 Externalerror,Incomingevent 02:09:25.096AM04/18/1994 Event2
4、33of500:EventID16#2942 I/Oaccesserror,reading Parea,double-wordaccess,Accessaddress:166 RequestedOB:I/OaccesserrorOB(OB122) Priorityclass:1 Externalerror,Incomingevent 02:09:25.084AM04/18/1994 最佳答案 I/O访问错误组织块(OB122) 描述 只要在访问模块上的数据时出错
5、,CPU的操作系统即调用OB122。例如,如果在访问I/O模块上的数据时,CPU检测到读取错误,操作系统将调用OB122。 了解I/O访问错误OB的操作 执行OB122时所处优先级与中断OB的优先级相同。如果OB122未编程,则CPU将由RUN模式改变为STOP模式。 S7提供了下列SFC,用于在执行程序期间屏蔽和取消屏蔽OB122的启动事件: SFC36(MSK_FLT):屏蔽特定的错误代码 SFC37(DMSK_FLT):取消屏蔽由SFC36屏蔽的错误代码 SFC38(READ_ERR):读取错误寄存器
6、 你看看是不是哪个多余的wordaccess,Accessaddress没有定义。 可以参考—— http://www.ad.siemens.com.cn/service/answer/solution.asp?Q_id=64317&cid=1029 http://www.ad.siemens.com.cn/service/answer/solution.asp?Q_id=22938&cid=1029