1、电伴热带的安装细节与配件详细设计指导一、管线伴热1、工艺参数:介质维持温度℃环境最低温度℃最高操作温度:a.连续操作温度b.扫线操作温度管材管径mm管道长度m保温材料保温层厚度mm环境:a.室内或室外b.地面或埋地c.防爆或非防爆d.防腐或非防腐电压2、散热量计算Q =q×Δt×K×C×E(w/m)Q -----每米管道的散热量(W/m)q -----管道的散热量(1℃/m时)TW -----维持温度TH -----环境最低温度Δt ---- TW–THK -----保温材料导热系数C ---------管道材料修正系
2、数E -----安全系数例:管径80mm,管道长度100m,管材为碳钢,介质为原油,维持温度50℃,环境最低温度-10℃,保温材料岩棉,保温层厚度25mm,计算每米管道热损失。(1)、计算温差Δt=TW–TH=50-(-10)=60(2)、计算每米管道的散热量K=0.044 (查表一“保温材料导热系数”)q=15.26 (查表二“每米管道1℃温差时的热损失”)C1=1 (查表三“管道材料修正系数”)E=1.2(一般取值为1.2)Q=q×Δt×K×C×E=15.26×60×0.044×1×1.2=48.36W/m即,每米管道热损失为48.3
3、6W。保温材料的保温系数、导热系数(10℃时)表一保温材料保温系数(w/m℃)导热系数(w/m℃)玻璃纤维0.036岩棉0.044矿渣棉0.038发泡塑料0.042珍珠岩0.047聚氨脂泡沫塑料0.024聚苯乙烯泡沫塑料0.031硅酸钙0.054复合硅酸盐毡FHP-VB0.0234每米管道1℃温差时的热损失Q表二管径保温层厚度(mm/in)101/2153/4251351-1/2502602-1/275310041/2158.866.735.744.593.943.613.282.953/42010.347.876.565.094.433.94
4、3.613.2812512.319.027.555.914.924.434.103.611-1/43214.7710.838.706.735.584.924.593.941-1/24017.0612.3010.017.556.235.584.924.2725019.6914.1111.328.537.056.075.424.762-1/26523.1316.5713.139.687.886.896.075.2538027.5619.3615.2611.169.037.886.895.743-1/29531.0121.8217.0612.3110
5、.018.537.556.23410034.4524.1218.8713.6210.839.198.216.734-1/211537.9026.4120.5114.7711.8110.018.867.22513041.8329.0422.4816.0812.8010.839.527.71615049.2233.9626.2518.5414.6012.3010.668.70820063.1643.1533.1423.1318.2115.0913.1310.661025077.7652.9940.5228.0521.8218.0515.5912.4
6、71230091.7062.1847.5832.8125.4321.0017.8814.2714350100.4068.0851.8435.6027.5623.4619.3615.2616400114.277.2758.7340.3631.0125.4321.8217.0618450128.186.4665.7944.9534.4528.2224.1218.8720500141.995.8172.6849.5537.9031.0126.4120.5124600169.6114.286.4658.7344.9537.0831.0124.12管道材
7、料修正系数表三管道材料修正系数碳钢1铜1.05不锈钢0.9塑料0.65阀门及管道附件散热系数(以每米管道散热量为基数)表四名称散热系数法兰0.5蝶阀0.7节流阀0.7球阀0.8球心阀1.2闸阀1.33、确定电伴热带型号、长度(1)、确定型号规格型号最高伴热温度℃最高耐温℃最大使用长度mDBR系列自调温电伴热带7510530DBR系列自调温电伴热带751051000ZBR系列自调温电伴热带1051351000Q总=Q×LQ---每米管道的散热量(W/m)L---管道长度4、电伴热带预留长度法兰: 管径的5倍弯头: 管径的1.5倍阀门: 管径的5倍
8、管架: 管径的3~5倍电源接线盒:预留1米中间接线盒:预留米0.5米4、电伴热带总长=电伴热带×安全系数注:安全系数(一般取值1.2)6、电伴热带敷设
此文档下载收益归作者所有