1、10kV线路损耗计算1、线路资料线路长度:7km,导线型号:JKLYJ-150,配变容量:2800kVA2、线路参数计算:20℃时铝绞线交流电阻率:31.5Ω·mm2/km,则R=L·ρ/S=7×31.5/150=1.47Ω。3、损耗计算⑴、按用户功率因数达0.9来计,只考虑有功电量。P=UIcosφI=P/(Ucosφ)(U=10.5kVcosφ取0.9R=1.47Ω)ΔP=3*I2R=0.01646P2(w)=1.646×10-5P2(kw),即线路有功功率损耗与有功负荷的平方成正比。P总=P+ΔP同时乘以等效时间τ,即电量W总=W+ΔW。ΔW=ΔPτ=1.64
2、6×10-5P2τ=1.646×10-5PW=1.646×10-5W2/τ按一班制,等效时间τ取240小时,则ΔW=6.86×10-8W2(kw·h)(W单位为kw·h)即线路有功电量损耗与用户有功电量的平方成正比。⑵不考虑功率因数达标,同时考虑有功电量和无功电量。ΔP=R*(P2+Q2)/1000U2(除1000是将R折算为kΩ)ΔW=ΔPτ=R*(W2+V2)/1000U2τ(U=10.5kVR=1.47Ω)按一班制,等效时间τ取240小时,则ΔW=ΔPτ=1.47*(W2+V2)/26460000=5.56×10-8(W2+V2)(kw·h)(W单位为kw·h
3、,V单位为kvar·h)两种方式计算比较:JKLYJ-150导线7公里线损计算有功电量无功电量功率因数KpΔWp线损率pKpqΔWpq线损率pq15000007260000.96.86E-0815435010.29%5.56E-0815440510.29%12000005808000.96.86E-08987848.23%5.56E-08988198.23%9000004356000.96.86E-08555666.17%5.56E-08555866.18%6000002904000.96.86E-08246964.12%5.56E-08247054.12%3000
4、001452000.96.86E-0861742.06%5.56E-0861762.06%200000968000.96.86E-0827441.37%5.56E-0827451.37%100000484000.96.86E-086860.69%5.56E-086860.69%有功电量无功电量功率因数KpΔWp线损率pKpqΔWpq线损率pq15000004920000.956.86E-0815435010.29%5.56E-081385599.24%12000003936000.956.86E-08987848.23%5.56E-08886787.39%90000
5、02952000.956.86E-08555666.17%5.56E-08498815.54%6000001968000.956.86E-08246964.12%5.56E-08221693.69%300000984000.956.86E-0861742.06%5.56E-0855421.85%200000656000.956.86E-0827441.37%5.56E-0824631.23%100000328000.956.86E-086860.69%5.56E-086160.62%有功电量无功电量功率因数KpΔWp线损率pKpqΔWpq线损率pq150000011
6、250000.86.86E-0815435010.29%5.56E-0819546913.03%12000009000000.86.86E-08987848.23%5.56E-0812510010.43%9000006750000.86.86E-08555666.17%5.56E-08703697.82%6000004500000.86.86E-08246964.12%5.56E-08312755.21%3000002250000.86.86E-0861742.06%5.56E-0878192.61%2000001500000.86.86E-0827441.37%5
7、.56E-0834751.74%100000750000.86.86E-086860.69%5.56E-088690.87%由此可见,采用同时考虑有功电量和无功电量计算方式较为客观,在功率因数为0.9时,两种方式线损一致。在功率因数低时,线损增加。若要采用固定线损率方式,根据配变容量2800kVA,每月电量估计在30~40万度,固定线损率取2.4%较为合理。