1、Design,ImplementationandCommissioningofaRemedialActionSchemeDistribuTECHConferenceandExhibitionSanDiego,CaliforniaJanuary25-27,2005By:RalphD.Kurth,P.Eng.RobertB.Henderson,P.Eng.Dr.R.S.(Bob)Burton,P.Eng.BrentS.Hancock,P.Eng.JamesN.Roik,P.Eng.ʧTeshmont1AbstractIntoday’sincreasinglyinterconnectedelectr

2、icalworld,theprotectionoftheelectricalnetworkitselfisjustasimportantastheprotectionoftheindividualelementsthatmakeupthenetwork.RemedialActionSchemes(RAS)aredesignedtomonitorandprotectelectricalsystemsbyautomaticallyperformingswitchingoperationsinresponsetoadversenetworkconditionstoensuretheintegrity

3、oftheelectricalsystemandavoidnetworkcollapse.ThispaperexaminesonesuchsystemdevelopedtoprotectaportionofanelectricalnetworkinthesoutherninteriorofBritishColumbia,Canada.ThesystemutilizesanumberofdifferentIntelligentElectronicDevices(IEDs)interconnectedusingavarietyofnetworkingandcommunicationsystemst

4、oformanintegratedschemecapableofperformingautomatedsheddingofloadandgenerationtoavoidcollapseoftheregionalelectricalnetwork.Thepaperoutlinesthedesignofthissystem,beginningwithcomprehensivesystemstudiesperformedtoexamineanddeterminetherequirementsoftheRAS.Theimplementationofthesystemisdiscussedinclud

5、ingthearchitectureofthesystemaswellastheselectionofIEDsusedandtheroleeachplaysintheoverallscheme.Finally,themethodsemployedtocommissiontheschemearealsoprovided.2IntroductionInthesoutherninteriorofBritishColumbia,Canada,naturalresourcecompanyTeckComincoMetalsLimited(TCML)operatesanelectricalpowersyst

6、emthatconsistsofaloadofapproximately220MWatitssmeltingoperationsinTrail,BCandahydrogeneratingstationwithacapacityofapproximately400MWlocatedsome15kmawayatWaneta.ThissystemisconnectedtotheWesternGridthroughinterconnectionswithadjacentutilities.Theseinterconnectionscomprise230kVand63kVconnectionswithF

7、ortisBCattheWarfieldTerminalStation(WTS)andeitherBCHydroorBPAat230kVattheWanetaGeneratingStation.ThesinglelinefortheregionisprovidedinFigure2-1.Figure2-1:SingleLineDiagramofRegionalNetworkDistribuTECH