欢迎来到天天文库
浏览记录
ID:9292141
大小:60.00 KB
页数:10页
时间:2018-04-26
《cleaning and chemical treatment of - alberta ministry of infrastructure:清洗和化学处理-阿尔伯塔基础设施部》由会员上传分享,免费在线阅读,更多相关内容在教育资源-天天文库。
1、SectionCoverPageSection23 25 19CleaningandChemicalTreatment2013-04-04ofSteamBoilerSystemsUsethisSectiontospecifythechemicalcleaningandtreatmentofsteamboilersystems.RefertoSection23 25 02foracompletelistofsectionsrelatedtoChemicalCleaningandTreatmentofMechanicalSyst
2、ems.ThisMasterSpecificationSectioncontains:.1ThisCoverSheet.2DataSheet-ReferenceStandards.2DataSheet-GuidelinesforRenovatedSystems.3SpecificationSectionText:1.General1.1Intent1.2RelatedRequirements1.3ReferenceDocuments1.4PerformanceRequirements1.5Submittals2.Produc
3、ts2.1CleaningChemicals2.2ChemicalTreatmentMaterials2.3WaterTestEquipment3.Execution3.1EquipmentInstallation3.2CleaningGeneral3.3PreBoilerEquipmentCleaningProcedure3.4BoilerCleaningProcedure3.5DepositRemovalProcedure3.6CleaningDirectSteamCulinaryBoilersandSteriliz
4、ers3.7OperationMaintenanceuntilInterimAcceptance3.8WasteWaterandMaterialDisposal3.9ChemicalCleaningandTreatmentScheduleforRenovatedSystemsBMSBasicMasterSpecificationAlbertaInfrastructureMasterSpecificationSystemPage0DataSheet-GuidelinesforRenovatedSystemsSection23
5、25 19CleaningandChemicalTreatment2012-11-09ofSteamBoilerSystems1.Whenanyofthefollowingworkhasbeenperformed,nocleaningisrequiredbutloosedepositsmustbeflushedoutbeforefloodingwithsystemwater..1Aminoramountofnewpipingisaddedtothesystemwhencomparedwiththeentiresystem..
6、2Converterisretubed..3Lessthanapproximately50%ofthetubesarereplacedinafiretubeorwatertubeboiler.2.Newpipingwhichcanbeisolatedfromtherestofthesystem:.1Cleanpipingusingthechemicalcleanerandprocedurespecifiedin2.1.3and3.4..2Chemicallytreattheentiresystemwithacorros
7、ioninhibitorspecifiedin2.2and3.7.3.Newpipingwhichcannotbeisolatedfromtherestofthesystem:.1Cleanthedepositsfromtheentirepreboilersystemasspecifiedin2.1.3and3.5..2Cleantheentiresystemwiththechemicalcleanerandprocedurespecifiedin2.1.1and3.3and3.4..3Chemicallytreatthe
8、entiresystemwithacorrosioninhibitorspecifiedin2.2and3.7.4.Firetubeboilerswheremorethanapproximately50%ofthetubesinafiretubeboilerarereplaced:.
此文档下载收益归作者所有