1、第27卷第11期电力系统及其自动化学报Vo1.27No.112015年11月ProceedingsoftheCSU-EPSANOV.2015高压输电线路单相故障性质诊断方法冷崇富,江亚群,黄纯,潘志敏27刘琨z,梁勇超z(1.湖南大学电气与信息工程学院,长沙410082;2.湖南省电力公司检修公司,长沙410002)摘要:输电线路单相接地故障性质识别方法是自适应重合闸实现的关键。依据故障相首端电压在瞬时性故障和永久性故障下二次电弧阶段高频能量特性的不同,提出了基于小波包变换和支持向量机的输电线路单相故障性质诊断方法。首先,对故障相首端电压信号进行小波包分解,为反映高频能量特
2、性去除低频频带,再将剩下频带的能量归一化后作为支持向量机的特征向量;通过训练学习样本使分类器建立特征向量和故障类型的映射关系,达到区分故障性质的目的。与已有的判据相比,该方法简单、易于实现,适用于带并联电抗器和不带并联电抗器的输电线路。关键词:输电线路;自适应重合闸;二次电弧;支持向量机;小波包变换中图分类号:TM76文献标志码:A文章编号:1003—8930(2015)11-0046—05DoI:10.3969~.issn.1003—8930.2015.11.008MethodtoDiagnosePropertyofSingle-phaseFaultonHigh-volt
3、ageTransmissionLinesLENGChongfu,JIANGYaqun,HUANGChun,PANZhimin,LIUKun,LIANGYongchao(1.CollegeofElectricalandInformationEngineering,HunanUniversity,Changsha410082,China;2.MaintenanceCompany,HunanElectricPowerCompany,Changsha410002,China)Abstract:Thekeypointofrealizingtheadaptivereclosureist
4、ofindawaytodistinguishthefaultpropertyofthetrans—missionlinewhenithappensthesingle-phasegroundingfault.Basedonwaveletpackettransformandsupportvectormachinetechnique.anewmethodisproposedtodistinguishpermanentfaultandtransientfaultaccordingtotheirdif-ferentenergypropertiesunderhighfrequencyd
5、uringtheperiodofthesecondarcofthefaultphasevoltageatthefirstend.TheVoltagesignalofthefaultphaseatthefirstendisdecomposedbywaveletpacketatfirst.andthebandwithalowfrequencyisremovedfromtheoriginalsignalinordertohighlightingthecharacteristicsofhighfrequencyenergy,Then.theremainingenergyisnorm
6、alizedtoformthefeaturevectorofthesupportvectormachine.Throughtrainingsamples,themappingrelationshipofclassifierisbuiltbetweenthefeaturevectorsandthefaulttypes.Inthisway,thepropertyofthesingle-phasegroundingfaultcanbeeasilydistinguished.Comparedwiththeexistingcriterion,thepro—posedmethodism
7、oresimple,easytoimplementandissuitableforapplyingontransmissionlinewithandwith—outshuntreactors.KeywordsItransmissionline;adaptivereclosure;secondarc;supportvectormachine;waveletpackettransform运行数据统计表明,超、特高压长距离输电线免了盲目重合带来的不良后果。路上的故障大多数是单相接地故障,瞬时眭故障目前,故障性质诊断分别在