1、系统说明(systemdescription)一、室内外消火栓系统:(indoor&outdoorfirehydrantsystem)参照GBJ16-87(2001年版)《建筑设计防火规范》,室内消火栓设计水量10L/s,室外消火栓设计水量45L/s。本次工程室内外消火栓系统,火灾延续时间按2小时。同一时间内.的火灾次数均按1次,因此一次消防用水量为396m³。AccordingtoGBJ16-87(2001edition)《CodeforArchitecturalDesignFireFighting》,fire

2、waterdemandflowofindooris10L/s,and45L/sofoutdoor.Firelasttimeis2hoursinthisproject,andfireoccursjust1timeinthesametime.Thetotaldemandoffirewateris396m³duringthefire.室内外消火栓给水系统采用临时高压给水系统,由蓄水池、加压泵、供水管、阀门、室内消火栓、气压罐等组成。Thehydrantsystemadoptsprovisionalhigh–pressu

3、resystemwhichiscomposedofcistern,pressuringpump,airpressuretank,supplywaterpipe,valveandfirehydrantindoor,etc.蓄水池采用地下钢筋混凝土结构,贮存有消火栓系统所需消防水容积400m3,室内室外消火栓加压水泵设电泵、柴油泵各一台,其中柴油泵为主泵,参数均为:Q=60L/s,H=50m.H2O,自灌式吸水,设于地下水泵房内;气压给水设备一套,XQB-1.0/6.0-L气压罐有效水容积6000L。Theciste

4、rnadoptsundergroundRCcistern,andeffectivedimensionis400m3,Pressuringwaterpumpforboththefirehydrantindoor&outdoorhaseachsetofelectricpumpanddieselpump,itsparametersis:Q=60L/s,H=50m.H2O,(thedieselpumpisasstandby)self-irrigatedabsorbinthefireprotectivewaterpumpr

5、oomwhichisunderground.Asetofwatersupplyofairpressure,XQB-1.0/6.0-L,theeffectivedimensionoftheairpressuretankis6000L.室内外消火栓系统全厂布置(包括实验楼、办公楼、厂房、仓库),明装管道采用镀锌钢管,卡箍连接;埋地管道采用球墨铸铁管,橡胶圈承插连接。Thefirehydrantpipesaredisposedalloverofthefactoryarea(includingexperimentbuil

6、ding,officebuilding,workshop,storage).Thepipeexposureinstalledshallbegalvanizedsteelpipe,connectedbyhoopclamp.Theundergroundpipeshallbegraphitecastironpipe,connectedbyrubberwasherandfemaleconnection.一、灭火器配置系统:(Setupoffireextinguishers)参照GB50140-2005《建筑灭火器配置设计

7、规范》。配置手提式磷酸铵盐干粉灭火器MF/ABC4,按中危险级设置。全厂布置。AccordingtoGB50140-2005,therequirementsofthe《designstandardforsetupoffireextinguisherinarchitecture》,thedangerdegreeoffireextinguishersetupsiteinthisprojectismiddle-danger-level,Itadoptsphosphoruspowderfireextinguishermo

8、untedincorporatedfirehydrantboxorinfireextinguisherbox.Setupsitecoversthewholefactory.三、喷淋系统:(firesprinklersystem)参照GB50084-2001《自动喷水灭火系统设计规范》及NFPA标准,办公楼实验楼按轻危险级设计,喷水强度4L/min.m2,作用面积160m2