欢迎来到天天文库
浏览记录
ID:39395905
大小:2.12 MB
页数:79页
时间:2019-07-02
《Elie wind farm interconnection facilities study》由会员上传分享,免费在线阅读,更多相关内容在学术论文-天天文库。
1、ElieWindFarmInterconnectionFacilitiesStudyPerformedby:ManitobaHydroSystemPlanningDepartmentProjectLeader:DavidJacobson,P.Eng.PrincipalContributors:RebeccaBrandt,P.Eng(TransgridSolutionsInc.)GerryLaneGlennEvansBrentJorowskiMikeWonsiakJeffLaningaMay2006(RevisedAppendixD-Added
2、ProjectSchedulesJuly24,2006)(Revised–re-evaluatedneedforSTATCOMwithTurbineAConnectionOptionB,Sept29,2006)ExecutiveSummaryAnInterconnectionFacilitiesStudy(IFS)hasbeenperformedtodeterminetheManitobaHydroInterconnectionFacilitiesandInterconnectionSystemandNetworkUpgradesnecess
3、arytoconnect99MWofwindgenerationnearthetownofElie,Manitobafromthepointdesignatedforthelocationofthegenerationfacility.Twooptionsforinterconnectionwereconsidered.OptionA:the99MWEliewindfarmwouldtap230kVlineD12Capproximately30kmfromDorseyandsectionalizethelinewithathree-break
4、erringbus.OptionB:the99MWEliewindfarmwouldadvancethe30kmDorsey-Eliesectionofaplannednew230kVDorsey-Portageline.ThenewDorsey-PortagelinewouldbetappedatElieviaasingle230kVbreaker,creatingathree-terminallinewhentheremainingElie-Portagelineisbuilt.ACcontingencyanalysiswasperfor
5、medforN-1andN-2contingenciesduringsystemintactconditions,andN-1contingenciesduringcritical230kVprioroutages.TherewerenoN-1thermaloverloadsimpactedbytheEliewindfarmthatrequiredfurtherinvestigation.ThereforenoNetworkUpgradesorInterconnectionSystemUpgradesarerequired.TheManito
6、baHydroTransmissionSystemInterconnectionRequirements(TSIR)[1]statethattheGeneratormustprovidereactivesupplythatisabletocontrolthevoltagelevelattheElie230kVbusbyadjustingtheMachine’spowerfactorbetweenaminimumof0.95overexcitedand0.95underexcitedatthegeneratorintermediatebuswi
7、thaminimumresponsetimeof15seconds.ForOptionA,theTurbineAwindturbineswouldneedadditionalVARsupportintheformof3x10MVArswitchedcapacitorsplusan8MVArSTATCOMonthe34.5kVbus.ForOptionB,theTurbineAwindturbineswouldneedadditionalVARsupportintheformof4x10MVArswitchedcapacitorsonthe34
8、.5kVbus.ForeitherOptionAorB,theTurbineBwindturbineshaveareactivesupplyrangefrom0.9
此文档下载收益归作者所有