1、ElieWindFarmInterconnectionFacilitiesStudyPerformedby:ManitobaHydroSystemPlanningDepartmentProjectLeader:DavidJacobson,P.Eng.PrincipalContributors:RebeccaBrandt,P.Eng(TransgridSolutionsInc.)GerryLaneGlennEvansBrentJorowskiMikeWonsiakJeffLaningaMay2006(RevisedAppendixD-Added

2、ProjectSchedulesJuly24,2006)(Revised–re-evaluatedneedforSTATCOMwithTurbineAConnectionOptionB,Sept29,2006)ExecutiveSummaryAnInterconnectionFacilitiesStudy(IFS)hasbeenperformedtodeterminetheManitobaHydroInterconnectionFacilitiesandInterconnectionSystemandNetworkUpgradesnecess

3、arytoconnect99MWofwindgenerationnearthetownofElie,Manitobafromthepointdesignatedforthelocationofthegenerationfacility.Twooptionsforinterconnectionwereconsidered.OptionA:the99MWEliewindfarmwouldtap230kVlineD12Capproximately30kmfromDorseyandsectionalizethelinewithathree-break

4、erringbus.OptionB:the99MWEliewindfarmwouldadvancethe30kmDorsey-Eliesectionofaplannednew230kVDorsey-Portageline.ThenewDorsey-PortagelinewouldbetappedatElieviaasingle230kVbreaker,creatingathree-terminallinewhentheremainingElie-Portagelineisbuilt.ACcontingencyanalysiswasperfor

5、medforN-1andN-2contingenciesduringsystemintactconditions,andN-1contingenciesduringcritical230kVprioroutages.TherewerenoN-1thermaloverloadsimpactedbytheEliewindfarmthatrequiredfurtherinvestigation.ThereforenoNetworkUpgradesorInterconnectionSystemUpgradesarerequired.TheManito

6、baHydroTransmissionSystemInterconnectionRequirements(TSIR)[1]statethattheGeneratormustprovidereactivesupplythatisabletocontrolthevoltagelevelattheElie230kVbusbyadjustingtheMachine’spowerfactorbetweenaminimumof0.95overexcitedand0.95underexcitedatthegeneratorintermediatebuswi

7、thaminimumresponsetimeof15seconds.ForOptionA,theTurbineAwindturbineswouldneedadditionalVARsupportintheformof3x10MVArswitchedcapacitorsplusan8MVArSTATCOMonthe34.5kVbus.ForOptionB,theTurbineAwindturbineswouldneedadditionalVARsupportintheformof4x10MVArswitchedcapacitorsonthe34

8、.5kVbus.ForeitherOptionAorB,theTurbineBwindturbineshaveareactivesupplyrangefrom0.9