《南方电网10kv干式变压器技术参数表》由会员上传分享,免费在线阅读,更多相关内容在行业资料-天天文库。
1、表5.1-1SC(B)10型三相干式电力变压器技术参数表序号项目技术参数要求1额定电压10/0.4kV2高压相数三相3低压相数三相四线4额定容量kVA3050801001251602002503154005006308001000125016005高压分接范围%±2×2.5或±56额定电流A1.732.894.625.777.229.2411.5514.4318.223.128.936.446.257.772.292.47额定频率Hz508空载损耗W1902703704004705406207208809801160130015201
2、770209024509负载损耗WF级(120℃)7101000138015701850213025302760347039904880596069608130969011730H级(145℃)7601070148016901980228027102960373042805230640074608760103701258010总损耗WF级90012701750197023202670315034804350497060407260848099001178014180H级950134018502090245028203330368046
3、10526063907700898010530124601503011空载电流%2.32.21.71.71.51.51.31.31.11.11.10.90.90.90.90.912短路阻抗%444444444446666613噪音水平(声功率级)dB6363656566666767696970717272747514噪音水平(声压级)dB50505050505050505050505050505252注:空载损耗实测值允许偏差应在3%以内,负载损耗实测值允许偏差应在5%以内,总损耗实测值允许偏差应在4%以内,空载电流实测值允许偏差30
4、%以内,短路阻抗实测值允许偏差10%以内;噪声水平按国家标准《6kV~500kV级电力变压器声级》(JB/T10088)给定的为声功率级值,由于在实际使用(测量)中多应用声压级,上表按声压级给出噪音水平。《声环境质量标准》(GB3096)内数值为声压级。损耗按南方电网公司《配电变压器能效标准及技术经济评价导则》(Q/CSG11624)的要求。表5.1-2SC(B)11型三相干式电力变压器技术参数表序号项目技术参数要求1额定电压10/0.4kV2高压相数三相3低压相数三相四线4额定容量kVA30508010012516020025031
5、54005006308001000125016005高压分接范围%±2×2.5或±56额定电流A1.732.894.625.777.229.2411.5514.4318.223.128.936.446.257.772.292.47额定频率Hz508空载损耗W1702403303604204805506407908801040117013601590188022009负载损耗WF级(120℃)7101000138015701850213025302760347039904880596069608130969011730H级(145℃)7
6、601070148016901980228027102960373042805230640074608760103701258010总损耗WF级88012401710193022702610308034004260487059207130832097201157013930H级93013101810205024002760326036004520516062707570882010350122501478011空载电流%2.32.21.71.71.51.51.31.31.11.11.10.90.90.90.90.912短路阻抗%444
7、444444446666613噪音水平(声功率级)dB6363656566666767696970717272747514噪音水平(声压级)dB50505050505050505050505050505252注:空载损耗实测值允许偏差应在3%以内,负载损耗实测值允许偏差应在5%以内,总损耗实测值允许偏差应在4%以内,空载电流实测值允许偏差30%以内,短路阻抗实测值允许偏差10%以内;噪声水平按国家标准《6kV~500kV级电力变压器声级》(JB/T10088)给定的为声功率级值,由于在实际使用(测量)中多应用声压级,上表按声压级给出噪
8、音水平。《声环境质量标准》(GB3096)内数值为声压级。损耗按南方电网公司《配电变压器能效标准及技术经济评价导则》(Q/CSG11624)的要求。