1、内蒙古电力技术42INNERMONGOLIAELECTRICPOWER2014年第32卷第6期doi:10.3969~.issn.1008—6218.2014.06.015220kV输电线路直角挂板断裂原因分析田峰,郭心爱,李红,田力男(内蒙古电力科学研究院,呼和浩特010020)FractureReasonAnalysisofRectangularHangingPlatein220kVTransmissionLineTianFeng,GuoXinai,LiHong,TianLinan(InnerMongoliaPowerResearchInstitute
2、,Hohhot010020)Abstract:Accordingtothefractureonrectangularhangingplatein220kVtransmissionline,analysisthefracturereasonsbyappearanceanalysis,microstructuredetection,impacttest,chemicalcompositiontest,scanningelectronmicroscopeSEM,energydispersivespectrometerEDSetctestmethod.Theres
3、ultsshowed:therewerealotofbrittlenessofsilicateinclusionsandaluminumcalciumsilicateinclusionsinbendingparts,crackingoccurredwhenbending,andinthesubsequentprocessofgalvanizing,Znpenetratethefracture;inthebearingservicestage,crackextensionforforce,thefinalcompletefracture.Suggestedm
4、anufacturerschoosepurityhighermaterialtoproductrectangularhangingplate;beforeinstallation,rectangularanglehangingplateneedednondestructiveinspectionofmacroscopicdetectionormagneticparticleinspection,verifieditsexistenceoforiginalcrack,inordertopreventtherectangularhangingplatefrac
5、tureandlinefault.Keywords:transmissionline;rectangularhangingplate;fracture;zincblock;silicatinctusions1输电线路及直角挂板概况塔I回中,Hz一10型直角挂板突然断裂。线路为双回输电线路,长2x27.7km;共85基铁塔,导线型号2013年4月某220kV输电线路停运期间29号LGJ一2x300/25,地线型号LGJ一95/55,采用36芯OP一【收稿日期】2014—10—24[作者简介】田峰(1979一),男(满族),内蒙古人,硕士,高级:[程师,从事火
6、电厂及电网金属材料失效分析T作。[基金项目]内蒙古电力(集团)有限责任公司2013年第二批科技项目(510141130023)