1、一、铜铝排载流量铜铝排15×320×325×330×440×440×550×550×660×660×8(宽/厚)铝排开启平放1622122643684855406607408731018铝排开启 竖放1712752853355105807057759201070铝排封闭 130175215315400440540605718837每米重量(kg)铝排0.400.530.661.041.401.742.182.613.134.18铜排开启平放127166205283372417515573680788铜排开启 竖放134175215300395440546600715830铜排封闭 104
2、136168235305342422470560648每米重量(kg)铜排0.120.160.200.320.430.540.680.810.971.30铜铝排60×80×680×880×100×100×100×120×120×2根2根10106810810(宽/厚)60×680×8铝排开启平放11401115127014301356156517851860198013401950铝排开启竖放11951205137015401475168518701955217014102120铝排封闭 935915104011701120128014201485162610171530每米重量(kg)
3、铝排5.224.185.576.965.226.968.708.3510.506.2611.14铜排开启平放89586499511151070122013701420155010351510铜排开启竖放935935107012001160131514751550176010901650铜排封闭 73070881591588510001120117712707861191每米重量(kg)铜排1.621.301.732.161.622.162.702.603.241.946.46二、塑料铜芯线载流量列表导线截面(mm2)11.52.54610硬线BV:根数/直径1/1.131/1.371/1
4、.761/2.241/2.737/1.33软线BVR:根数/直径7/0.437/0.5219/0.4119/0.5219/0.6419/0.82开启式载流量51015253560封闭式载流量4812202848导线截面(mm2)162535507095120硬线BV:根数/直径7/1.687/2.117/2.4919/1.8119/2.1419/2.4937/2.01软线BVR:根数/直径49/0.6498/0.58133/0.58133/0.68189/0.68259/0.68259/0.76开启式载流量90113140177268288314封闭式载流量729311514522024
5、0258三、说明1.根据电流大小,按上表选择相母线。2.零(N)母线按相母线截面的一半选取(但≮16mm2)。3.由于受元件进出线端口宽度的限制或母排不易满足规定的电气间隙时,可用对应塑胶线代替。4.开启式载流量:架空、平敷等情况时的电缆载流量;封闭式载流量:穿管、埋设等情况时的电缆载流量。