1、ZYQ-824电压切换箱使用说明书Ver1.02005.07目录1装置简介··········································1-11.1应用范围·········································1-11.2装置配置·········································1-12装置使用说明······································2-13装置调试大纲···············
2、·······················3-13.1一般检查··········································3-13.2继电器检查········································3-13.3装置整组检验······································3-24其他··············································4-14.1包装、贮存及运输············
3、······················4-14.2随机文件··········································4-14.3订货须知··········································4-15附图···············································5-15.1ZYQ-824端子接线图·······························5-15.2ZYQ-824装置原理图(1)·····
4、·······················5-25.3ZYQ-824装置原理图(2)····························5-35.4切换插件原理图··································5-45-5ZYQ-824电压切换箱使用说明书1.装置简介1.1应用范围该装置适用于单母线分段接线系统,可作为保护绕组及测量绕组的电压重动或PT并列回路选用。1.2装置配置装置共一层箱,由三个插件组成,包括三个电压切换插件,均采用后插拔式,保证了配置的灵活方便,5-5Z
5、YQ-824电压切换箱使用说明书5-5ZYQ-824电压切换箱使用说明书5-5ZYQ-824电压切换箱使用说明书1.装置使用说明本章内容主要针对装置的外观、指示灯进行了详细介绍。装置的正面面板布置图如下所示:图2-1装置的正面面板布置图面板信号灯从上往下依次是I~II母电压及电压并列动作指示。“I~II母电压”为红灯,当电压取自I~II母线相应点亮。“电压并列”为红灯,当两段母线PT并列时点亮。5-5ZYQ-824电压切换箱使用说明书1.装置的调试大纲装置在出厂前均作了详细的调试检验与调整,但为了避免由
6、于运输的振动或保管不当而造成机械性能变化,需要作一般的检查和调试,检查和调试均可按插件接线图以插件为单元进行。3.1一般检查装置接线应符合原理接线,各元件规格正确,装配完好,焊接坚固牢固,接插可靠。各导电部分对外壳(或框架)以及电气上无联系的各电路之间的绝缘电阻,应不小于100MΩ(用500V兆欧表测量)。3.2继电器的检查检查1YQJ1~9、2YQJ1~9、3YQJ1~9的动作电压为30%~70%额定电压,复归电压为30%~80%额定电压(1YQJ7~9、2YQJ7~9、3YQJ7~9的返回电压为不小
7、于5%额定电压),动作时间不大于10ms.3.3装置整组检验3.3.1按装置原理图,通电检查各引出端子上触点的闭合和开断状况,要求接线正确,接触良好。3.3.2在端子101和132上加上可调电压(+)、(—),检查1YQJ1~9的动作情况,同时面板上“I母电压”灯亮,在端子102和132上加上可调电压(+)、(—),检查1YQJ1~6的复归情况,检查1YQJ1~9各输出触点的通断情况,应符合装置原理图的要求。3.3.3在端子201和232上加上可调电压(+)、(—),检查2YQJ1~9的动作情况,同时面
8、板上“II母电压”灯亮,在端子202和232上加上可调电压(+)、(—),检查2YQJ1~6的复归情况,检查2YQJ1~9各输出触点的通断情况,应符合装置原理图的要求。3.3.4在端子301和332上加上可调电压(+)、(—),检查3YQJ1~9的动作情况,同时面板上“III母电压”灯亮,在端子302和332上加上可调电压(+)、(—5-5ZYQ-824电压切换箱使用说明书),检查3YQJ1~6的复归情况,检查3YQJ1~9各输出触点的通断